Is Smoke Control in Blocks of Flats Keeping Residents Safe?

Smoke control in blocks of flats helps protect escape routes, reduces the spread of smoke and supports firefighters during an emergency. But do you know what your building’s automatic opening vents are supposed to do, whether they operate correctly and how much the building’s fire safety strategy depends on them?

Imagine you’re managing a residential block containing 30 flats.

There’s an automatic opening vent on each landing, another at the top of the staircase and a smoke control panel near the main entrance.

You’ve probably walked past this equipment hundreds of times without giving it much thought.

The maintenance contractor visits periodically, and you receive a certificate confirming that the automatic opening vents have been serviced.

Everything appears to be in order.

But what would happen if a fire started in a second-floor flat and smoke entered the communal corridor?

Would the correct vent open? Would smoke be directed away from the protected staircase? Could firefighters still use that staircase to reach the fire, and would the system operate correctly if smoke spread to another floor?

More importantly, does anybody responsible for managing the building actually know how the system is supposed to work?

The problem with smoke control in blocks of flats is that individual vents can appear to operate correctly while the complete system fails to provide the protection the building relies upon.

And where a building has only one protected staircase, that could have serious consequences for residents and firefighters.

So why do residential buildings need smoke ventilation, how does it work alongside fire doors and compartmentation, and when might it provide additional protection where a building has other fire safety challenges?

Why Do Blocks of Flats Need Smoke Ventilation?

One of the most dangerous things about a building fire isn’t necessarily the flames. It’s the smoke.

Smoke can spread quickly, reduce visibility, make breathing difficult and expose occupants to toxic gases. Even where the fire remains within one room, smoke can affect adjoining spaces and escape routes.

In a block of flats, this becomes particularly important because residents and firefighters may depend on the same communal staircase.

Imagine a fire developing inside a third-floor flat.

When the occupants open their front door to escape, some smoke may enter the communal corridor or lobby. Even if the flat entrance door subsequently closes correctly, smoke may already be present outside the flat.

Without suitable precautions, that smoke could spread towards the staircase and affect people attempting to leave the building.

The Government’s Approved Document B, Volume 1, specifically recognises that smoke is likely to enter communal corridors or lobbies during a flat fire.

The guidance therefore recommends providing appropriate smoke ventilation to help control smoke movement and protect the common staircase.

This provides additional protection alongside the fire doors and compartment walls separating the different parts of the building.

The distinction is important.

In many purpose-built residential blocks, the primary objective of smoke ventilation is to help protect the staircase, rather than guarantee that every communal corridor remains completely clear of smoke.

The staircase may be the only protected route available to residents who need to evacuate. It’s also an important access route for firefighters bringing equipment into the building.

Keeping smoke out of that staircase, or limiting the amount entering it, is therefore a fundamental part of the building’s fire safety arrangements.

How Does Smoke Ventilation Actually Work?

Smoke ventilation systems use natural or mechanical means to control the movement of smoke.

Natural systems generally rely on smoke’s buoyancy, together with suitable openings, to provide a route for smoke to escape.

Mechanical systems use fans and associated equipment to extract smoke or maintain pressure differences between protected areas.

The type of system installed depends on the building’s design, height, layout and fire safety strategy.

Automatic Opening Vents

Automatic opening vents, commonly called AOVs, are frequently used in residential developments.

They may take the form of windows or louvres in communal corridors, staircases or smoke shafts.

When the appropriate smoke detector operates, the control system opens the relevant vents.

In a straightforward natural ventilation arrangement, this allows smoke entering the communal corridor to escape through an external opening.

The vent at the head of the staircase may also operate, depending on the design.

This can reduce smoke accumulation and help protect the staircase from smoke entering through the doors separating it from the corridor.

However, opening a vent doesn’t automatically guarantee that smoke will travel in the intended direction.

Wind conditions, temperature differences, the location of openings and the building’s geometry can all influence smoke movement.

This is one reason why smoke ventilation should be designed as a complete system rather than simply installing automatic windows wherever space is available.

Natural Smoke Shafts

Some residential blocks use a vertical smoke shaft serving several floors.

Rather than ventilating directly through an external window, the system allows smoke from the affected corridor or lobby to enter a dedicated shaft and discharge at roof level.

Approved Document B describes an arrangement where detection on the affected floor causes the relevant corridor vent, smoke shaft outlet and staircase vent to operate together.

The vents connecting all the other floors to the smoke shaft should remain closed.

That last point is particularly important.

If vents on other floors open when they shouldn’t, the shaft could create a route for smoke to spread between levels.

A smoke control system isn’t working correctly simply because the vents open. They need to open and close in the correct sequence.

Mechanical Smoke Extract

Mechanical systems use fans to extract smoke from communal corridors or lobbies.

These systems can provide greater control over smoke movement and may be used in buildings where natural ventilation is difficult to provide.

However, they also introduce additional technical requirements involving fans, power supplies, controls, dampers and the construction of smoke extract shafts.

The Smoke Control Association’s technical resources include guidance on the design, maintenance and performance of smoke control systems serving common escape routes in apartment buildings.

Its guidance recognises the importance of considering wind effects, pressure differences and the complete system’s performance.

Mechanical systems can provide valuable protection, but they need competent design, commissioning and maintenance.

How Does Smoke Ventilation Help Firefighters?

Smoke ventilation isn’t provided solely for residents.

It can also assist fire and rescue crews when they enter the building.

Imagine firefighters arriving at a block where smoke has entered the communal corridors.

They need to establish which floor is affected, locate the fire and move equipment through the protected staircase.

If the staircase is heavily smoke-logged, those operations can become considerably more difficult.

Smoke ventilation may help reduce smoke entering the staircase, improve conditions in affected lobbies and support access to the fire floor.

The system may also provide manual controls that firefighters can use during an incident.

For example, a staircase-head vent may be operated by firefighters to assist with smoke clearance, while a more complex smoke control system may incorporate controls for the relevant vents or fans.

However, these controls need to be suitable for the particular design and clearly identified.

Residents and untrained maintenance staff shouldn’t interfere with specialist smoke control controls simply because they want additional ventilation.

London Fire Brigade’s guidance for residential building owners and managing agents specifically explains that smoke ventilation can assist both means of escape and firefighting operations.

It also warns that defective or altered systems can compromise the intended protection.

For managing agents and RTM companies, the important point is that smoke ventilation isn’t simply a convenience feature.

It may be an essential part of the facilities firefighters rely upon when dealing with a fire in the building.

Can Smoke Ventilation Compensate for Other Fire Safety Shortcomings?

This is where smoke control becomes particularly interesting.

A well-designed system can provide additional protection that helps a building achieve its overall fire safety objectives.

In certain circumstances, smoke control may also form part of a fire-engineered solution where a building’s layout differs from a conventional design.

But there’s an important distinction between providing enhanced protection and using smoke ventilation to justify deficiencies elsewhere.

Example 1: Protecting a Single Staircase

Imagine a residential block served by one protected staircase.

Residents from several floors rely on that staircase to leave the building, while firefighters use it to reach upper floors.

The building’s fire safety strategy depends on the staircase remaining sufficiently protected from smoke.

Fire-resisting walls and doors provide the primary separation between the staircase and the accommodation.

Smoke ventilation provides an additional layer of protection by helping control smoke entering the adjoining corridors or lobbies.

This can be particularly valuable when a flat entrance door is opened during evacuation and smoke escapes into the common parts.

But smoke ventilation doesn’t mean fire doors can be left defective or wedged open.

The two precautions have different functions and are intended to work together.

Example 2: Buildings With Longer Escape Routes

Smoke ventilation can influence the design of communal escape routes.

For example, Approved Document B recognises that in certain small single-stair residential layouts, a travel distance of 4.5 metres may be increased to 7.5 metres where the specified additional smoke control is provided.

This is a useful illustration of how suitable smoke control can support a particular building layout.

However, it isn’t a general permission to increase travel distances in every residential building simply because an AOV has been installed.

More complex or extended travel distances may require a specifically developed fire-engineered solution.

The designer would need to demonstrate how the proposed smoke control system, fire-resisting construction, detection arrangements and means of escape work together.

The Smoke Control Association’s guidance on common escape routes in apartment buildings provides specialist information for designers considering these arrangements.

The relevant building control requirements and the building’s fire strategy must also be considered.

Example 3: Improving Protection in an Older Building

Consider an older residential block with a communal corridor that has limited natural ventilation.

The building may have been designed under earlier guidance, and its smoke ventilation arrangements might not resemble those expected in a new development.

A fire risk assessment could identify concerns about smoke entering the protected staircase.

Depending on the building, improving the existing ventilation or introducing a suitably designed smoke control system might be one possible way of improving protection.

However, the solution needs to be based on a proper understanding of the existing construction, evacuation strategy and risks.

It shouldn’t simply involve installing an automatic window and assuming the problem has been solved.

There may be other appropriate improvements involving fire doors, compartmentation, detection or changes to the building’s management arrangements.

A competent fire safety specialist should establish which measures are necessary and whether the proposed combination provides suitable protection.

Example 4: Buildings Where Occupants May Need More Time to Evacuate

Smoke control may also provide valuable additional protection where occupants could require more time to leave the building.

For example, some residents may have reduced mobility or need assistance from firefighters.

In these circumstances, protecting communal escape routes for as long as reasonably necessary can be particularly important.

Where a building has evacuation lifts, the current Approved Document B guidance also recognises the need to protect evacuation shafts, including the relevant lift lobbies.

However, smoke ventilation isn’t a substitute for suitable evacuation arrangements, sufficient fire-resisting construction or the other precautions necessary to protect residents.

It is one part of the overall fire safety strategy.

Can Smoke Control Make Up for Defective Fire Doors or Compartmentation?

Not automatically. This is a distinction that every Responsible Person should understand.

Imagine a block of flats where several flat entrance doors don’t close properly.

A contractor suggests that the automatic smoke ventilation system will deal with any smoke escaping into the corridor.

That’s not a satisfactory assumption.

The doors are intended to restrict the spread of fire and smoke at source. The smoke control system is intended to manage smoke that may nevertheless enter the communal areas.

If the fire doors fail to provide the intended separation, the smoke control system could be exposed to conditions beyond those for which it was designed.

The same issue arises where compartment walls or floors contain unsealed service penetrations.

Smoke could spread through concealed routes that the smoke ventilation system was never intended to control.

The Association for Specialist Fire Protection (ASFP) publishes extensive technical guidance on fire doors, compartmentation, fire-stopping, fire-resisting ductwork and smoke control dampers.

Its guidance emphasises the importance of these passive fire protection measures working as part of the building’s overall fire safety design.

The ASFP’s specialist guidance also addresses the construction of smoke shafts and the importance of suitable fire-resisting materials and components.

These are not simply ventilation ducts. They may form part of the building’s fire-resisting construction and must prevent unwanted fire and smoke spread between floors.

Smoke control can enhance protection and support a carefully designed fire safety solution. It should not be used as an excuse to ignore defective fire doors, missing fire-stopping or inadequate compartmentation.

Where additional smoke control is proposed to address a particular fire safety shortcoming, the overall solution should be assessed and justified by somebody with appropriate fire engineering competence.

Why Does the Construction of the Smoke Shaft Matter?

This is an area that can be overlooked during routine maintenance.

A smoke shaft isn’t simply a convenient vertical void that carries smoke out of the building.

It may connect several floors and must be constructed so that smoke from the affected floor is controlled without creating an unintended route into other parts of the building.

The construction of the shaft, its openings, dampers and associated fire-resisting elements all matter.

For example, if contractors install new cables or services through the shaft wall without suitable fire-stopping, its fire-resisting performance may be compromised.

Similarly, replacing a smoke control damper with an unsuitable component could affect the performance of the installation.

The ASFP’s technical publications include Advisory Note 36 on smoke shaft construction materials and its Grey Book guidance on smoke control dampers to BS EN 12101-8.

These provide useful technical references when considering the construction and protection of smoke shafts.

A smoke control maintenance engineer may confirm that an actuator or damper operates correctly.

But that doesn’t automatically establish that the surrounding shaft construction remains suitable.

Where defects or alterations are suspected, a separate compartmentation investigation may be necessary.

This is why the fire risk assessment, smoke control servicing and compartmentation records should be considered together.

What Common Smoke Control Defects Should Managing Agents Look For?

Some problems are immediately obvious, while others can remain undetected until the system is tested.

A control panel may display a fault or isolation indication. An actuator may have failed, leaving a vent unable to open.

A window might be stuck open, allowing rainwater into the building, or obstructed by decoration or stored materials.

Sometimes residents interfere with vents because they want additional ventilation or are trying to stop draughts.

In other cases, the problem develops during maintenance or refurbishment work.

An automatic opening window could be replaced without reinstating the original control arrangements, or new building services might compromise a smoke shaft.

There may also be problems with the system’s cause-and-effect programming.

For example, smoke detection on one floor might operate the wrong vent, fail to open the staircase vent or allow other floors to open when they should remain closed.

These faults can be more difficult to identify through simple visual checks.

London Fire Brigade specifically warns that smoke ventilation systems in residential buildings have sometimes been found not to operate as intended.

Its guidance highlights the need to verify the correct sequence of operation, including ensuring that smoke shaft vents on unaffected floors remain closed.

The important thing is that the Responsible Person understands what the system is designed to do and has arrangements to confirm that it continues to operate correctly.

How Often Should Smoke Control Systems Be Tested?

Under Article 17 of the Regulatory Reform (Fire Safety) Order 2005, necessary fire safety equipment must be subject to suitable maintenance arrangements and kept in efficient working order and good repair.

Where smoke control forms part of the building’s fire safety precautions, it needs appropriate inspection, testing and maintenance.

The legislation doesn’t prescribe one universal servicing interval for every smoke control system in every residential building.

The appropriate maintenance programme depends on the equipment, manufacturer’s instructions, applicable technical standards and the building’s fire safety arrangements.

The Government’s Fire Safety in Purpose-Built Blocks of Flats guidance recommends monthly routine testing of automatic opening vents and electrically controlled vents using their manual controls.

It also recommends testing associated smoke detectors and controls at least annually, following the manufacturer’s instructions.

More complicated systems, including mechanical smoke extract and pressurisation installations, require specialist maintenance appropriate to their design and operating requirements.

The Smoke Control Association’s maintenance guidance provides additional industry information on maintaining these systems.

The important distinction is between a simple routine functional check and comprehensive specialist servicing.

A suitably instructed caretaker may be able to carry out prescribed routine checks.

But investigating actuators, control circuits, smoke shaft dampers, mechanical fans and the complete operating sequence requires the appropriate technical competence.

What Are the Legal Requirements for High-Rise Residential Buildings?

For high-rise residential buildings in England, additional statutory requirements apply.

Under Regulation 7 of the Fire Safety (England) Regulations 2022, the Responsible Person must undertake monthly routine checks of essential firefighting equipment.

These duties apply to multi-occupied residential buildings at least 18 metres in height or containing at least seven storeys.

Smoke control systems are included within the equipment covered.

The Regulations also include associated fire detection and alarm systems, including detectors linked to smoke control equipment.

The Home Office’s guidance on these requirements explains that the monthly checks should establish whether the system responds to the relevant detection equipment and any manual controls provided for firefighters.

These checks are additional to professional servicing and maintenance.

The Responsible Person must keep records of the monthly checks and make those records accessible to residents.

What Happens if a Smoke Control Fault Cannot Be Repaired Within 24 Hours?

This is particularly important for high-rise residential buildings.

Where a relevant fault is identified, the Responsible Person must take steps to rectify it.

If the fault cannot be rectified within 24 hours, Regulation 7 requires notification to the local fire and rescue authority by electronic means as soon as reasonably practicable.

The authority must also be informed electronically when the fault has been repaired.

The 24-hour period is a reporting trigger, not permission to leave a serious defect unattended for a day.

The Responsible Person must consider the effect of the fault immediately and determine whether temporary precautions are necessary.

That could involve additional supervision, changes to building management arrangements or other measures appropriate to the circumstances.

The fire risk assessment may also need reviewing, particularly where the impairment is significant or likely to remain unresolved.

Reporting the defect to the fire service doesn’t remove the responsibility to arrange repairs.

What Should a Smoke Control Maintenance Report Actually Tell You?

A maintenance certificate stating that the AOV system has been serviced is useful, but it doesn’t necessarily tell you whether the complete system operates correctly.

The report should identify the equipment tested, the checks undertaken, any limitations and the defects discovered.

Where the installation depends on particular cause-and-effect arrangements, the maintenance programme should include appropriate verification of those functions.

For example, a smoke shaft system may require smoke detection on a particular floor to open that floor’s vent, the staircase vent and the shaft outlet, while keeping vents on other floors closed.

Testing each vent individually from the control panel doesn’t necessarily prove that the correct sequence will occur automatically during a fire.

The London Fire Brigade’s guidance for managing agents specifically identifies the importance of verifying this operation.

A useful report should also identify whether any components were inaccessible, whether parts of the system remained disabled and what remedial work is required.

Where defects are identified, the Responsible Person needs to ensure that they are addressed and retain evidence of completion.

The maintenance report should demonstrate what was tested and what remains outstanding, not simply that an engineer attended the building.

What if Nobody Knows How the Original System Was Designed to Work?

This is a common difficulty in older buildings or those that have changed managing agents several times.

The original designer or installer may no longer be involved.

The operating instructions might be missing, and nobody can locate the cause-and-effect information.

The building has automatic opening vents and a control panel, but there is no clear record of what should happen when a detector operates.

Without that information, it can be difficult to determine whether the system is functioning correctly.

For new building work, Regulation 38 of the Building Regulations 2010 requires relevant fire safety information to be provided to the Responsible Person.

That information can include the design and operating arrangements for smoke control systems.

For existing buildings, the managing agent should first try to obtain the original information from the developer, installer, previous management company or available building records.

Where that information cannot be recovered, a competent smoke control specialist may need to investigate the installation and establish its intended operation.

This is particularly important where the building’s fire strategy relies on smoke ventilation to support extended travel distances, protect a single staircase or provide other enhanced protection.

A competent specialist should be able to explain what the system is designed to achieve and whether the installed equipment can demonstrate that performance.

Do Older Buildings Need Their Smoke Ventilation Upgrading?

Not automatically.

Some older residential blocks have manually openable windows or permanent vents rather than modern automatic smoke control systems.

Others were constructed using smoke dispersal arrangements that are no longer accepted for new developments.

The Government’s purpose-built flats guidance recognises that older smoke dispersal arrangements have often proved unreliable.

However, it doesn’t follow that every older block must automatically be fitted with a new mechanical smoke extract system.

The existing arrangements need to be considered in the context of the building’s construction, evacuation strategy, fire risk assessment and relevant design standards.

The first priority is establishing whether the existing system operates as intended.

Where the arrangements are deficient, further investigation may identify appropriate improvements.

Those might involve repairing existing equipment, improving ventilation, addressing compartmentation defects or developing a different fire-engineered solution.

The scope of the work should be justified by the risks rather than simply applying every current new-build recommendation retrospectively.

What Should the Fire Risk Assessment Say About Smoke Control?

A suitable fire risk assessment should identify the smoke control arrangements where they form part of the building’s fire safety precautions.

The assessor should establish what type of system is provided, whether suitable maintenance arrangements exist and whether significant faults or limitations have been identified.

The assessment should also consider whether the system remains appropriate for the building’s current layout, evacuation strategy and fire safety arrangements.

For example, if the building has been altered since the smoke control system was installed, those changes may affect its intended operation.

A new partition might obstruct a vent. A replacement window might have removed part of the original system, or new services could have compromised a smoke shaft.

Where the fire risk assessment identifies serious concerns, it may recommend further investigation by a competent smoke control specialist.

However, a routine fire risk assessment isn’t a substitute for comprehensive technical testing or a complete smoke control design validation.

At ESI: Fire Safety, we consider it important to distinguish between a defect that can be identified during a normal assessment and a specialist technical question requiring further investigation.

For example, we may identify that an AOV panel displays a fault, the maintenance records are incomplete or a smoke shaft has questionable construction.

Those findings can be recorded and appropriate specialist action recommended.

But demonstrating the full smoke movement performance of a complex mechanical extract system may require detailed engineering assessment, specialist testing or computational fluid dynamics modelling.

The role of the fire risk assessment is to identify whether the relevant risks are being suitably managed and whether further expertise is necessary.

Why Should Managing Agents and RTM Companies Take Smoke Control Seriously?

For landlords, managing agents, RTM companies and residents’ management companies, smoke control should form part of the building’s ongoing fire safety management programme.

That means understanding what equipment is installed, identifying who maintains it and ensuring that inspection and testing records remain available.

It also means following up defects rather than simply filing away the maintenance certificates.

If a smoke control contractor reports a defective vent or failed actuator, the Responsible Person needs to understand its significance and arrange appropriate remedial action.

Where the building is high-rise, the additional monthly checking, recording and fault-reporting duties must also be met.

The management arrangements should ensure that records remain accessible when contractors or managing agents change.

Residents also need appropriate information about the building’s fire safety arrangements.

Under Article 21A of the Fire Safety Order, Responsible Persons for buildings containing two or more sets of domestic premises must provide residents with relevant and comprehensible fire safety information.

In practical terms, residents should understand that smoke control equipment isn’t something to interfere with.

An automatic opening vent might look like an ordinary window, but it may form an important part of the building’s fire safety strategy.

Residents should know how to report damage, obstruction or unexpected operation.

So, Would the Smoke Vent on Your Landing Actually Protect You?

Smoke ventilation is easy to overlook because most systems spend their working lives doing very little.

A vent may remain closed for months, and a smoke extract fan may never operate outside routine testing.

But during a fire, the system can become important to controlling smoke movement, protecting communal escape routes and assisting firefighters.

In some buildings, smoke control also forms part of a wider fire-engineered strategy, providing enhanced protection or supporting particular design arrangements.

However, it must work alongside suitable fire doors, compartmentation, detection and evacuation procedures.

It cannot simply be assumed to compensate for defective fire-resisting construction or other significant shortcomings.

The Responsible Person needs to know what the system is intended to achieve, ensure that appropriate testing and maintenance take place and understand the consequences of any defects.

The question isn’t simply whether your block has smoke ventilation. It’s whether the complete system provides the protection the building’s fire safety strategy depends upon.

A maintenance certificate is useful evidence, but understanding what has been checked, what remains outstanding and whether the system is still suitable is what effective fire safety management requires.

Need Independent Advice About Smoke Control in Your Building?

At ESI: Fire Safety, we help freeholders, managing agents, RTM companies and residential property managers understand the fire safety arrangements within their buildings.

Our services include fire risk assessments, fire safety consultancy, compartmentation assessments, fire door inspections and ongoing fire safety management support.

While we don’t design, install or service smoke control systems, we can review their role within a building’s fire safety arrangements, examine maintenance records, identify relevant concerns and recommend where specialist investigation is necessary.

We can also help establish whether proposed improvements form part of a suitable fire safety strategy, particularly where an existing building has complicated escape arrangements, compartmentation concerns or an older smoke ventilation installation.

Through our Dedicated Fire Safety Manager service, we support managing agents and RTM companies with compliance records, inspection schedules, contractor coordination and monitoring outstanding remedial actions.

With more than 25 years of experience in electrical safety and fire safety compliance, we provide practical advice for those responsible for residential blocks and mixed-use developments.

Our service areas include Bishop’s Waltham in Hampshire, Epsom in Surrey, Finchampstead in Berkshire, Seaford in East Sussex, Paddock Wood in Kent, Bampton in Oxfordshire and Southfields in South West London, together with surrounding areas.

Whether your AOV system has outstanding faults, the original smoke control documentation is missing or you’re unsure whether existing arrangements provide suitable protection, we can help establish the next steps.

ESI: Fire Safety — No Shortcuts in Safety.

Contact ESI: Fire Safety, call 01276 300 351 or email office@esifiresafety.co.uk to discuss your fire risk assessment or ongoing fire safety management requirements.

This article focuses on smoke control arrangements in residential buildings in England. The general duties under the Regulatory Reform (Fire Safety) Order 2005 also apply in Wales, while the additional checking and reporting duties under the Fire Safety (England) Regulations 2022 apply in England only. The suitability of existing smoke control systems should be assessed against their intended design, condition and the risks associated with the building.

Picture of Jamie Morgan <h5>MIFSM MIFPO MSFPE MIET</h5>

Jamie Morgan

MIFSM MIFPO MSFPE MIET

Jamie Morgan is the founder and Principal Consultant at ESI: Fire Safety. With more than 25 years’ experience across fire safety, electrical engineering and technical compliance, he helps building owners and managers work out what needs attention first and what will work day to day. His work spans fire risk assessments, fire strategies, compliance reviews and DSEAR assessments, backed by hands-on experience designing and implementing life safety systems and electrical safety management.

Growing up around the timber-framed cottages and oast houses of rural Kent gave Jamie a lasting interest in historic and heritage buildings. He brings that interest to his work with churches and listed properties, finding ways to improve fire safety while preserving the features that give them their character.

Jamie holds a Level 6 Diploma in Fire Risk Assessment and a Level 5 qualification in Fire Engineering Design. That combination helps him explain how a building’s design affects fire risk, why a recommendation matters and what it means for the people who use the building. You can check his Intermediate registration on the National Fire Risk Assessors Register.

Jamie keeps up with developments in the profession through his memberships of the Institute of Fire Safety Managers, the Society of Fire Protection Engineers, the Institute of Fire Prevention Officers, the British Fire Services Association and the Institution of Engineering and Technology, which he joined in 2007. He also holds supporter membership of the Institute of Heritage Building Conservation and membership of Society for the Protection of Ancient Buildings.