Does a Church Need a Written Fire Risk Assessment?

Yes. If your church is in England or Wales, it needs a fire risk assessment, and that assessment must be written down in full. That has been the law since 1 October 2023. It applies whether you have a congregation of fifteen or three hundred, and whether you employ ten people or none.

Many churches don’t know this. For years the rule was different, and some of the guidance churches rely on still describes the old rule. This post explains why a church fire risk assessment is a legal duty, what changed in 2023, what your written record must contain, and who can carry it out.

Why every church needs a fire risk assessment

The Regulatory Reform (Fire Safety) Order 2005, known as the Fire Safety Order or FSO, applies to almost all non-domestic premises in England and Wales. A church is non-domestic. So is a church hall, a church office and a chapel of rest.

The FSO places its duties on the “responsible person”. The Home Office guide for small and medium places of assembly, which covers churches holding up to 300 people, explains who that is. In a workplace it is the employer and anyone else with control of the premises. In all other premises it is the person or people in control.

That second part is why a church with no employees still needs a church fire risk assessment. Someone controls the building. For a Church of England parish, the Legal Advisory Commission of the General Synod says that is the PCC, acting as a body. The Institution of Fire Engineers’ guide for traditional church buildings says the same, and notes that boards of trustees play a similar role in some nonconformist churches.

The responsible person must carry out a suitable and sufficient fire risk assessment. It must pay particular attention to people at special risk, such as disabled people and children. It must then be acted on and kept under review.

The old rule about writing it down

Until October 2023, the FSO only required some premises to record their fire risk assessment. Pages 6 and 9 of the Home Office guide set out the old test. You had to record the significant findings if your organisation “employs five or more people, your premises are licensed or an alterations notice” was in force. Otherwise, writing it down was only described as good practice.

Most churches employ fewer than five people. Many are not licensed. So for a long time a small church could argue it had no legal duty to keep a written record, as long as it had done the assessment. The General Synod’s 2007 legal opinion on the FSO also described heavier record keeping as something that applied to churches with five or more employees.

That is no longer the law.

What changed on 1 October 2023

Section 156 of the Building Safety Act 2022 made a series of changes to the FSO. They came into force on 1 October 2023 in both England and Wales. The changes apply to all premises covered by the FSO, including every church.

The biggest change for churches is simple. GOV.UK guidance on the new duties says “you must now record the fire risk assessment in full (including all the findings)”. The five-employee threshold has gone. The licence and alterations notice triggers no longer matter for this. Every church must have a written fire risk assessment.

Other changes matter too.

  • The responsible person must record their fire safety arrangements. In plain English, that means writing down how fire safety is actually managed, not just what the risks are.
  • The responsible person must record their name and a UK address where notices can be sent.
  • If someone else carries out or helps with the assessment, their name and organisation should be recorded.
  • Where more than one responsible person shares a building, such as a church and a nursery or a regular hirer, they must find each other, share contact details and say which parts each is responsible for.
  • When a responsible person leaves, they must hand relevant fire safety information to whoever takes over.
  • Fines for some offences, such as impersonating a fire inspector or failing to comply with an inspector’s requirements, have increased.
  • The Home Office’s own guides now carry more weight in court. Following them, or departing from them, can be used as evidence of whether the FSO was breached.

The official guide hasn’t caught up

Here is the catch. The Home Office guide for small and medium places of assembly is still the main official guide for churches. It was first published in 2006. An accessible web version was added in August 2024. But both the PDF and the web version still describe the old five-employee rule on recording. Neither mentions the 2023 changes.

Some church guidance has the same problem. The Institution of Fire Engineers’ church guide still talks about a “record of significant findings”. Older diocesan leaflets and parish templates may say the same.

The guidance on how to assess fire risk in a church is still useful. Much of it is excellent. But on the question of whether you must write it down, the law has moved on and the guides have not. If the two disagree, follow the law. Record your church fire risk assessment in full.

What a written church fire risk assessment should include

Article 9 of the FSO now requires the record to include the findings of the assessment, the measures that have been or will be taken, and any group of people identified as especially at risk. Put together with the other 2023 changes, a complete written record for a church should cover these things.

  • The name of the responsible person, such as the PCC or trustees, and a UK address for notices.
  • The name of anyone who carried out or helped with the assessment, and their organisation.
  • A description of the buildings and how they are used, including services, events, hirers and any parish office.
  • The fire hazards found, such as candles, heating, electrics, kitchens, storage and the risk of arson.
  • The people at risk, including children, older people, disabled people, bell ringers, people working alone and visitors who don’t know the building.
  • The fire safety measures in place, such as escape routes, exits, alarms, emergency lighting, signs and extinguishers.
  • The actions needed, who will do them and by when.
  • The fire safety arrangements, meaning who checks what, how often, how the church is evacuated and who has been trained.
  • The date of the assessment and when it will next be reviewed.

A tick-box form with no findings and no actions isn’t a full record. The point of writing it down is that someone else, such as a new churchwarden, an insurer or a fire safety officer, can read it and understand how your church manages fire risk.

What a church fire risk assessment looks at

Churches have fire risks that most buildings don’t. A good church fire risk assessment will look at all of them.

  • Candles and matches, which the IFE guide says should be locked away when the church is unsupervised.
  • Heating, including under-pew heaters, which should be guarded and checked. The IFE guide says portable LPG heaters, hot air blowers and patio heaters should not be used.
  • Electrics, including old wiring, extension leads and temporary lighting for concerts and festivals.
  • Arson, which is a real risk for buildings left open or unattended.
  • Hot works by builders and roofers, which Historic England advises should only be carried out in historic buildings when there is no alternative.
  • Bell towers, where ringers need a reliable way to be warned and a safe way down.
  • Large congregations at weddings, funerals and Christmas, when more stewards may be needed.
  • People who need help to get out, including wheelchair users and parents with pushchairs.
  • Church halls and regular hirers, including nurseries and playgroups. I cover these in more detail in who is responsible for fire safety when a nursery uses a church hall.
  • A vicarage or parish office attached to the church. I explain when the FSO reaches a clergy house in does the Fire Safety Order apply to a church manse or vicarage.

If the church is listed, the assessment should also look for ways to improve fire safety without harming the historic fabric. Better management often achieves more than new hardware, and any physical changes may need a faculty or other consent first.

Who can carry out a church fire risk assessment?

The law doesn’t require a qualified fire risk assessor. The responsible person can carry out the assessment, or appoint a competent person to help. A competent person is someone with enough training, experience or knowledge to do the job properly.

The Home Office guide says it was written to help a responsible person assess less complex premises. If you read it and find you can’t apply it, you should get help from a competent person. More complex premises will probably need someone with comprehensive training or experience in fire risk assessment.

Church guidance encourages small churches to take ownership. The IFE guide gives templates so a small church can manage fire safety in-house. It also makes a good point. It is an advantage to involve a church member, because they know the building better than any outsider.

Doing it yourself can work well for a small, simple church with low-risk activities. I would recommend getting a competent fire risk assessor involved if any of these apply.

  • The church is large, listed or complicated, with galleries, crypts, towers or several linked buildings.
  • There is a church hall with regular hirers, a nursery or a café.
  • Large events happen, such as concerts, festivals or civic services.
  • Anyone sleeps on the premises, for example in a night shelter or on a youth weekend.
  • There is a fire alarm or emergency lighting system that nobody is quite sure about.
  • The last assessment is old, or nobody can find it.
  • You read the Home Office guide and didn’t feel confident applying it.

Since August 2025, BS 8674:2025 has set out a national framework for the competence of individual fire risk assessors. Registers such as the National Fire Risk Assessors Register (NFRAR), run by the Institute of Fire Safety Managers, list assessors whose competence has been independently checked. Both are worth looking at when you choose who to appoint.

What a professional fire risk assessor brings

A churchwarden who knows the building well is a real asset. But fire risk assessment is a specialist job, and the law keeps changing. A professional assessor brings four things a volunteer usually can’t.

The first is being up to date. Fire safety law and guidance have changed a lot since the Grenfell Tower fire, through the Fire Safety Act 2021, the Fire Safety (England) Regulations 2022 and section 156 of the Building Safety Act 2022. New British Standards for fire risk assessment and assessor competence followed in 2025. As this post shows, even the government’s own guide for churches hasn’t caught up with the 2023 change on recording. A professional assessor follows these changes as part of the job, so your assessment reflects the law as it stands today, not as it stood when the template was printed.

The second is insurance. A professional assessor should hold professional indemnity insurance, which can cover claims if their advice proves to be negligent. A volunteer filling in a template has no such cover, and the responsibility stays with the PCC or trustees. Always ask any assessor you appoint for proof of their professional indemnity and public liability insurance.

The third is experience. A professional assessor carries out fire risk assessments day in, day out. They see a wide range of buildings and know where problems hide. That means spotting the chained exit, the overloaded extension lead behind the organ, the missing fire stopping above the vestry ceiling or the storeroom full of gas bottles, which are exactly the kinds of things that appear in the enforcement cases below. It also means knowing what is proportionate, so you aren’t told to spend money you don’t need to.

The fourth is education. A good fire risk assessor doesn’t just hand over a report and leave. They walk round the building with you and explain what they are looking at and why. They answer your questions in plain English. Why does that door need to close on its own? Is the old fire alarm good enough? What should the stewards do at the Christmas carol service? By the end, the churchwardens and volunteers should understand their building’s fire risks far better than before. That knowledge stays with the church long after the visit, and it is what keeps fire safety working week to week.

Using a professional doesn’t remove your responsibility. The PCC or trustees remain the responsible person. But it gives you an assessment you can rely on, from someone accountable for it.

How often should a church review its fire risk assessment?

The FSO requires the assessment to be reviewed regularly, and whenever there is reason to think it is no longer valid or there has been a significant change. For a church, significant changes might include building works, a new heating system, a new hirer, a new pattern of services or a big event.

The law doesn’t set a fixed interval. The IFE guide suggests making fire safety a standing item at the annual meeting so the assessment is looked at alongside everything else. Some dioceses expect a review every twelve months. That is a sensible rhythm for most parishes, as long as you also review it when things change.

Each review should be recorded too. A note of the date, who reviewed it and what changed is enough if nothing significant has moved.

What happens if a church doesn’t have one?

The fire and rescue service enforces the FSO. The Home Office guide explains that inspectors will look for evidence that you have carried out a suitable fire risk assessment and acted on it. If they aren’t satisfied, they can issue an enforcement notice requiring improvements. In extreme cases they can issue a prohibition notice restricting the use of all or part of the building. Failing to comply with the FSO is a criminal offence.

Insurers take it seriously too. Ecclesiastical, which insures many churches, says a formal record must be made of significant findings and remedial measures. Not having a written church fire risk assessment could make a difficult conversation after a fire even harder.

Real cases of fire safety enforcement at churches

This is not a theoretical risk. Fire and rescue services do inspect churches, and they do take action. The cases below come from published fire and rescue service records and court reporting. Most involve independent churches meeting in converted industrial or commercial buildings. I haven’t named the churches that received notices, because the point is what went wrong, not who.

A church prosecuted after ignoring a prohibition notice

In 2007, London Fire Brigade served a prohibition notice on Mountain of Fire and Miracles Ministries International in Erith. The notice limited the ground floor to 600 people at any one time. When officers returned during a service in January 2008, they found around 1,200 people in the main hall.

They found much more. A fire exit was blocked by a heavy steel bar. The exit next to it was chained and locked. Eighteen LPG and butane gas bottles, some of them full, were stored haphazardly. Naked flame heaters were being used inside the hall. The church pleaded guilty to three breaches of the FSO and was ordered to pay £30,000 in fines and costs at Woolwich Crown Court in July 2009.

A prohibition notice followed by ten failures

In July 2022, London Fire Brigade served a prohibition notice on a church in south London. The notice cited a lack of fire separation between floors, no suitable way of warning people of a fire, and inadequate escape routes and exits. An enforcement notice followed two months later listing ten separate failures. Among them were:

  • the fire risk assessment had not been reviewed;
  • fire safety measures were not being managed, monitored or reviewed;
  • escape routes were not adequately lit;
  • there was no proper emergency plan;
  • fire safety equipment and the premises were not being maintained;
  • staff had not been given adequate fire safety training; and
  • outside organisations working on the premises had not been given fire safety information.

No fire alarm and blocked escape routes

In June 2020, London Fire Brigade served a prohibition notice on a church in east London. The premises had no suitable way of warning people of a fire. Its escape routes and exits had not been provided or kept clear and available for use.

Sleeping accommodation inside a church

In February 2023, Devon and Somerset Fire and Rescue Service served a notice on a church that had bedsits within the building. The required works included 30 minutes of fire resistance between the kitchen and the stairs, an interlinked fire alarm covering the bedsits and their escape routes, removing ignition risks from escape routes, and a second escape route for the bedsits through the minister’s office. The prohibition has since been withdrawn. Where anyone sleeps in or above a church, the standard expected rises sharply.

Findings that were never written down

In 2021, London Fire Brigade served an enforcement notice on a church in east London. The first requirement was to record the significant findings of the fire risk assessment, including the measures taken and any groups of people especially at risk. The notice also required a fire alarm, clear and properly lit escape routes, an emergency plan, proper maintenance and staff training. That notice was served before the 2023 changes. Today the requirement would be to record the assessment in full.

No fire risk assessment at all

In 2016, London Fire Brigade served an enforcement notice on the pastor of a church meeting in a commercial unit in east London. The church had no suitable and sufficient fire risk assessment. It also had no fire alarm, inadequate firefighting equipment, poor escape routes and lighting, and no emergency plan. The notice required the pastor to co-ordinate fire safety with the other responsible persons in the building.

A church as owner of residential accommodation

In September 2025, London Fire Brigade served an enforcement notice on a church as the owner of sleeping accommodation in south east London. It required the church to review its fire risk assessment regularly, manage its fire safety measures properly, provide lit and clear escape routes, prepare an emergency plan, maintain its equipment and appoint enough competent people to help.

The pattern

The same failures come up again and again. No fire risk assessment. An assessment that was never reviewed. Findings that were never recorded. No emergency plan. No fire alarm. Blocked, locked or unlit escape routes. Untrained staff and volunteers. Most of them would have been picked up by a proper church fire risk assessment, written down and acted on.

So does a church need a written fire risk assessment?

Yes, every church in England and Wales does. Since 1 October 2023 the church fire risk assessment must be recorded in full, along with the fire safety arrangements and the name and address of the responsible person. It doesn’t matter how small the church is or whether it employs anyone. If your church relied on the old five-employee rule, or on a guide that still describes it, now is the time to put it in writing.

How we can help

ESI Fire Safety is an independent fire safety consultancy. Our fire risk assessors are listed on the National Fire Risk Assessors Register (NFRAR), run by the Institute of Fire Safety Managers.

Our Principal Consultant, Jamie Morgan, has a special interest in historic and heritage buildings. He is a supporter of the Institute of Historic Building Conservation (IHBC) and the Society for the Protection of Ancient Buildings (SPAB). So when a church is old or listed, you have someone who understands both the fire safety and the heritage.

We work with churches, PCCs, trustees and diocesan property teams across Surrey, Berkshire, Hampshire, Sussex, Kent, London, Buckinghamshire and Oxfordshire. We can carry out a full church fire risk assessment, recorded to the post-2023 standard, or review one your church has done itself. Call us on 01276 300351 or email office@esifiresafety.co.uk.

This article is general guidance on fire safety law in England and Wales. It is not legal advice. Your diocese, district or insurer may have its own requirements.

Sources

Legislation and government guidance

Enforcement cases

Church, heritage and industry guidance

Picture of Jamie Morgan <h5>MIFSM MIFPO MSFPE MIET</h5>

Jamie Morgan

MIFSM MIFPO MSFPE MIET

Jamie Morgan is the founder and Principal Consultant at ESI: Fire Safety. With more than 25 years’ experience across fire safety, electrical engineering and technical compliance, he helps building owners and managers work out what needs attention first and what will work day to day. His work spans fire risk assessments, fire strategies, compliance reviews and DSEAR assessments, backed by hands-on experience designing and implementing life safety systems and electrical safety management.

Growing up around the timber-framed cottages and oast houses of rural Kent gave Jamie a lasting interest in historic and heritage buildings. He brings that interest to his work with churches and listed properties, finding ways to improve fire safety while preserving the features that give them their character.

Jamie holds a Level 6 Diploma in Fire Risk Assessment and a Level 5 qualification in Fire Engineering Design. That combination helps him explain how a building’s design affects fire risk, why a recommendation matters and what it means for the people who use the building. You can check his Intermediate registration on the National Fire Risk Assessors Register.

Jamie keeps up with developments in the profession through his memberships of the Institute of Fire Safety Managers, the Society of Fire Protection Engineers, the Institute of Fire Prevention Officers, the British Fire Services Association and the Institution of Engineering and Technology, which he joined in 2007. He also holds supporter membership of the Institute of Heritage Building Conservation and membership of Society for the Protection of Ancient Buildings.

Tags :

Share :

Facebook
Twitter
LinkedIn
Telegram

Related Articles

Speak to a fire safety consultant

Planning a fit-out, need a fire risk assessment or working through a compliance issue?

Bring your plans or questions and we’ll talk through what your project needs.