It was the Christmas holidays in 2012. The corridors at Lytchett Minster School in Dorset were empty, the staff were at home, and the school was as quiet as it ever gets. Then, on 27 December, lightning hit the building. By the time the fire was out, the roof had collapsed completely. The 400-seat theatre was gone. So was the A-level coursework that students had spent months on.
Nobody was hurt, and that matters more than anything else in this story. But it raises a question that lots of building owners have never thought to ask. Is lightning protection part of your fire risk assessment? And if it is, what should your assessor be looking at?
The short answer is yes, it should be.
Lightning is a real source of ignition, it hits buildings in Surrey, Berkshire and Hampshire every summer, and a good fire risk assessment looks at every likely way a fire could start.
This guide explains why, what the standards say, and what you should actually do about it. Along the way we’ll look at real lightning fires, from a medieval cathedral to a semi in Tilehurst, and what each one teaches.
Contents
- Why lightning belongs in a fire risk assessment
- What the law and the standards say
- How lightning actually starts a fire
- Case studies: lightning fires that changed buildings
- Lightning and commercial buildings
- Lightning fires close to home
- What a lightning protection system does
- Surge protection: the part people forget
- Which buildings are higher risk?
- Testing and inspection
- What to do next: a practical checklist
- Frequently asked questions
Why lightning belongs in a fire risk assessment
Every fire needs three things: something to burn, oxygen, and a source of heat to start it. A fire risk assessment works through all three. The heat part is what assessors call “sources of ignition”. Most people think of the obvious ones: faulty wiring, cooking, smoking, heaters, hot works, arson.
Lightning is a source of ignition too. It just arrives from outside instead of inside. A single strike can carry tens of thousands of amps, and when that current passes through roof timbers, insulation, metalwork or wiring, it can heat them to the point where they catch fire. It can also travel into a building along cables and pipes and start a fire somewhere nowhere near the roof.
Under the Regulatory Reform (Fire Safety) Order 2005, the responsible person for any non-domestic building has to carry out a “suitable and sufficient” assessment of the fire risks. The Order doesn’t list lightning by name. It doesn’t list most hazards by name. What it asks is that you look at the risks your building actually faces. If your building is tall, isolated, on a hill, has a spire or a thatched roof, stores flammable materials, or houses people who would struggle to get out, lightning is a risk worth looking at properly.
That’s why PAS 79, the publicly available specification most UK fire risk assessors work to, includes lightning in the list of things to consider. In practice it often gets a single line on the form: “Lightning protection: yes/no.” This guide is about what should sit behind that line.
What the law and the standards say
This is where people often get confused, so let’s take it piece by piece.
Is lightning protection a legal requirement?
Not as a blanket rule. There is no law that says every building must have a lightning protection system. The Fire Industry Association’s evaluation tool for existing residential buildings, published in June 2026, says plainly that lightning protection is “not a building regulation requirement”.
But that isn’t the end of it. The Fire Safety Order requires you to assess your risks and take reasonable steps to reduce them. If your assessment shows that lightning is a significant risk, you are expected to act on it. Insurers, especially for churches, heritage buildings, schools and industrial sites, often expect a system to be fitted and maintained. And if you already have a system, you have a duty to keep it working, because a fire safety measure that’s been allowed to decay isn’t protecting anyone.
BS EN 62305: the lightning protection standard
The British and European standard for lightning protection is BS EN 62305. It comes in four parts. The one that matters most for your fire risk assessment is Part 2, risk management. It sets out a method for working out whether a building needs protection, by weighing up things like the building’s size, location, construction, what it’s used for, how many people are inside, and what would be lost if it caught fire.
That last point is important. The standard doesn’t just look at the chance of a strike. It looks at the consequences: loss of life, loss of service to the public, loss of cultural heritage, and economic loss. A small rural barn and a listed church of the same height might score very differently, because of what’s inside.
A full BS EN 62305-2 risk assessment is specialist work. Your fire risk assessor doesn’t need to do it, but they should be asking whether one has been done, and whether its findings still match the building.
BS 7671: the wiring regulations
The wiring regulations, BS 7671, come at lightning from a different direction. They’re interested in what happens when a surge comes in along the electrical supply. Regulation 443.4.1 requires surge protection where an overvoltage could result in serious injury or loss of life, interruption of public services, or damage to cultural heritage. Section 534 then covers how surge protective devices (SPDs) are selected and installed, including where a building already has a lightning protection system.
We’ll come back to surge protection, because it’s the part of lightning safety most often missed.
The FIA screening tool for residential buildings
For existing residential buildings, such as blocks of flats, the Fire Industry Association published its Lightning Protection Existing Arrangements Evaluation Tool in June 2026. It’s a screening tool rather than a full risk assessment, and it gives a simple yes or no answer on whether the existing arrangements need further looking into. If you manage a block of flats, it’s a useful way to start the conversation with your assessor.
How lightning actually starts a fire
Lightning doesn’t always come in through the roof in a dramatic bolt. There are three main ways it starts fires in buildings, and a good assessment considers all of them.
1. A direct strike on the building
This is the one everyone pictures. Lightning hits the highest point, often a chimney, spire, roof ridge, aerial or a cross on top of a church. The current looks for the easiest route to the ground. If there’s no proper conductor, it goes through whatever it can find: damp timbers, metal fixings, pipework, wiring. Where it meets resistance, it creates intense heat. Dry roof timbers, felt and insulation can ignite almost instantly.
2. A surge along cables and pipes
Lightning doesn’t have to hit your building to get inside it. A strike on a nearby power line, a phone line, an aerial or even the ground can send a surge along any conductor that runs into the building. That’s what happened in Tilehurst.
In July 2017, lightning hit the TV aerial on a house in Oregon Avenue, Tilehurst, just outside Reading. The surge ran straight down the TV cable into the loft and started a fire there. A firefighter from Dee Road fire station said the surge also blew plug sockets off the walls inside the house. A father and son were evacuated, and crews from Wokingham Road and Dee Road had the fire out in about 40 minutes. But the electrical damage needed extensive repairs.
Tilehurst is a perfect illustration of why a fire risk assessment can’t stop at the roof. The fire started in the loft, but the danger came in through a cable. Every service that enters your building, whether it’s power, data, phone, an aerial or a satellite dish, is a possible route for a surge.
3. Damage to the systems that keep you safe
The third way is quieter, but it can matter just as much. A strike or surge can knock out your fire alarm, emergency lighting, door release systems or sprinkler pumps. A building can survive the strike itself and then be left without its safety systems until someone notices.
On 27 January 2025, lightning struck St Thomas More’s Catholic Primary School on Hook Lane in Havant. Hampshire and Isle of Wight Fire and Rescue Service said crews from Havant, Cosham, Southsea and Waterlooville were called after the strike caused the fire alarm to malfunction. Thankfully there was no fire. But the school was evacuated and then closed for roof repairs.
Notice two things about that one. First, it happened in January. Lightning isn’t only a summer problem. Second, the alarm was affected. If your fire risk assessment relies on a fire alarm to get people out, the assessment should also ask what happens to that alarm in a storm.
Case studies: lightning fires that changed buildings
These five stories span almost 500 years. In every one, the building, and the way people protected buildings like it, changed afterwards.
Old St Paul’s Cathedral, 1561
Long before Christopher Wren’s dome, London’s skyline was dominated by the medieval cathedral of Old St Paul’s, with one of the tallest wooden spires in Europe. On 4 June 1561, that spire caught fire and crashed through the roof of the nave. A newsheet published days afterwards blamed lightning.
The spire was never replaced. The rest of the building limped on until the Great Fire of 1666 finished it off. What stands out today is how little anyone could do. There was no such thing as a lightning conductor. Benjamin Franklin wouldn’t carry out his famous experiments for nearly two hundred years. A tall timber spire was simply a target, and when it was hit, the fire travelled downwards into the roof of the building below.
That pattern, of fire starting high and travelling through roof spaces, is exactly the one we still see in lightning fires today. The difference is that now we know how to stop it.
St James’ Church, Abinger Common, 1964
Here’s a Surrey story. St James’ Church in Abinger Common, in the hills between Dorking and Guildford, has had a remarkable twentieth century. In 1944, a flying bomb all but destroyed it. The west wall of the nave, the belfry, the spire and the whole nave roof came down. The village rebuilt it.
Then, in June 1964, during a storm across southern England, lightning struck the tower and set it on fire. The church’s own history describes the bolt striking deep into the base of the spire.
The church is still there, bombed and lightning-blasted, and very much used. But Abinger shows something that matters for anyone responsible for a church or a historic building. Rebuilding once doesn’t make you safe. A tower or spire on high ground is exposed every time a storm passes, and its protection has to be maintained for as long as the building stands. If you look after a historic building, our article on fire safety in historic buildings and what Windsor Castle teaches covers salvage and emergency planning in more depth.
York Minster, 1984
In the early hours of 9 July 1984, fire broke out in the roof of the south transept of York Minster. By the time it was over, 114 firefighters had attended, the transept roof was lost, and the damage came to £2.25 million.
The cause was almost certainly lightning hitting a metal electrical box in the roof space. Like many large historic buildings at the time, the roof void wasn’t divided up, so once the fire started it could spread along the timbers. Smoke detectors were in the wrong places to pick it up early, which gave the fire time to take hold.
Firefighters made a famous decision that night. They deliberately brought down the burning roof into the transept below, to stop the fire spreading along the rest of the building. It saved the Minster.
Afterwards, the roof was rebuilt with fire safety designed in. According to the National Churches Trust, the roof spaces are now divided into compartments to limit fire spread, with a fire monitoring and alarm system and an extensive lightning conductor installed.
That is the whole lesson of this article in one building. A lightning protection system to stop the strike starting a fire. Compartmentation to stop a fire spreading if one does start. Detection to find it early. If you’d like to understand the compartmentation side, our fire compartmentation guide explains how it works and what a survey looks for.
Lytchett Minster School, 2012
Back to where we started. On 27 December 2012, lightning struck Lytchett Minster School in Dorset during the Christmas break. The fire took the roof completely. The 400-seat theatre was destroyed, and with it students’ A-level coursework.
What happened next is a story about planning and community. The school reopened on 9 January, less than two weeks later, in temporary buildings that had been used for the London 2012 Olympics. The rebuild was finished in May 2015, more than two years after the strike.
Think about what that disruption means for a school, a care home or a business. It isn’t just the cost of the building. It’s two and a half years of temporary arrangements, lost work that can never be replaced, and the knock-on effect on everyone who uses the building. A fire risk assessment that considers lightning is partly about protecting lives. It’s also about protecting everything the building does.
St Michael and All Angels, Leigh Park, Havant
One more church, and this one is in Hampshire. One morning, just after Mass, lightning hit the cross on the roof of St Michael and All Angels Roman Catholic Church in Leigh Park, Havant. Parishioners saw it happen.
The fire destroyed the church, and it spread to the priest’s accommodation next door. The parish priest, Fr Joe Keller, told Independent Catholic News he only had time to grab his wallet and passport before the building was engulfed. The church’s £100,000 organ was lost, and loss adjusters estimated the claim at about £2 million.
There’s a detail in the diocese’s account that’s easy to miss. A teacher at a nearby school said they heard the bang and the sirens and were very worried, because some of the children had brothers and sisters at the playgroup in the church hall. The hall wasn’t damaged. But that’s the point. Church buildings are rarely just churches. They’re playgroups, community halls, food banks, meeting rooms and homes. When you assess the fire risk of a building like that, you’re assessing it for everyone who uses it, on every day of the week.
Lightning and commercial buildings
It’s easy to think of lightning as a problem for churches and old buildings with spires. But the Fire Safety Order covers all non-domestic premises, and lightning hits plenty of ordinary commercial buildings too. Here are four examples from the last few years, each with a different lesson.
A sheltered housing block in Peckham: fire inside the walls
On the afternoon of 5 August 2017, lightning hit a four-storey sheltered accommodation block on Commercial Way in Peckham, south London. London Fire Brigade said the fire was believed to have started when insulation between the internal and external walls on the fourth floor ignited after the strike.
Six fire engines and around 35 firefighters attended. Ten people were led to safety and nobody was hurt. But the fire was hidden inside the wall. Crews had to dismantle the walls around the affected area to reach the smouldering insulation, and it took four hours to bring the incident under control.
This one deserves attention from anyone who manages a block of flats, a care home or supported housing. The residents of a sheltered block are often older or less mobile, so the time it takes to get everyone out matters. And the fire didn’t stay where you could see it. It travelled through the cavity, which is exactly where cavity barriers are supposed to stop it. A cavity barrier is a strip of fire-resisting material fitted inside a wall or ceiling void to stop fire and smoke travelling through the hidden space. When they’re missing or damaged, a fire can move through a building without anyone seeing it.
A pub in Holland-on-Sea: losing the whole roof
On the morning of 20 June 2023, lightning struck a large pub on Frinton Road in Holland-on-Sea, Essex. Residents heard the strike and got out. By the time crews arrived, about half the roof was alight. Essex County Fire and Rescue Service used seven crews, an aerial ladder platform and a drone to find hotspots. The roof was completely destroyed and the pub was left uninhabitable.
Pubs, hotels and restaurants often have people sleeping upstairs, whether that’s staff, guests or the landlord’s family. That changes the fire risk assessment completely, because sleeping people are slower to react. If your business has residential accommodation above it, lightning and roof fires should be part of how you plan for a night-time evacuation.
Waste and energy sites in Oxfordshire: lightning and flammable gas
Just over the county border from Berkshire, two Oxfordshire sites show what happens when lightning meets flammable gas.
In June 2016, lightning ignited methane stored in a digester at the Agrivert food waste site in Benson, near Wallingford. The fireball destroyed the roof and caused around £250,000 of damage. Crews came from Oxfordshire, Buckinghamshire and Berkshire.
Then, on the evening of 2 October 2023, lightning struck a tank at Severn Trent’s anaerobic digestion plant at Cassington, near Yarnton. Thames Valley Police said lightning was believed to have struck gas containers. Residents reported an explosion and a fireball lit up the sky across Oxford. Around 40 firefighters attended, and it was reported that three of the site’s five tanks were damaged.
Nobody was hurt at either site. But if your business stores flammable gases, fuels, solvents or dusts, lightning is more than a roof risk. It’s an ignition source for anything that could explode. Those sites also fall under the Dangerous Substances and Explosive Atmospheres Regulations 2002 (DSEAR), which require you to assess and control ignition sources around flammable atmospheres. Lightning should be part of that assessment, and the fire risk assessment and the DSEAR assessment need to agree with each other.
Garages in Thatcham: how fast lightning fires spread
Closer to home, Royal Berkshire Fire and Rescue Service was called to a block of garages in Justice Close, Thatcham, after a lightning strike on a Monday afternoon in May. Two crews from Newbury and one from Dee Road attended, and members of the public raised the alarm quickly.
Station Manager Steve Beard said afterwards: “Although lightning strikes don’t happen very often, when they do, they can initiate severe damage and rapid fire spread.” He added that without prompt action, the fire would have spread to the properties next door.
Rare, but fast. That’s lightning in two words, and it’s why it belongs in your assessment even if your building has never been hit.
Lightning fires close to home
If you’re reading this from Camberley, Farnborough, Guildford or Reading, it might feel like these things happen somewhere else. They don’t. The Met Office records between 200,000 and 300,000 lightning strikes across the UK in a typical year, and south-east England sees more thunderstorms than anywhere else in the country. Here’s a sample of what our local fire services have dealt with.
- Bracknell, May 2026. Six months ago, a single lightning strike affected four homes on Westmorland Drive. Crews came from Bracknell, Ascot, Wokingham, Maidenhead, Windsor and Wokingham Road, with the aerial ladder platform from Whitley Wood. They were there for nearly four hours.
- Winnersh. Royal Berkshire crews were called to a roof on fire after a lightning strike in Reynards Close. Six firefighters in breathing apparatus put it out.
- Andover, July 2021. Lightning severely damaged two semi-detached houses on Mercia Avenue in the early hours. Crews came from Whitchurch, Overton, Winchester, Basingstoke and Rushmoor, with support from Dorset and Wiltshire. A 70-year-old woman was checked by paramedics but didn’t need hospital.
- Horley. Ten fire engines went to Campbell Grove after lightning is thought to have started a roof fire that spread to the house next door. Surrey crews, helped by West Sussex, fought it from around 5pm until 9.30pm.
- Epsom. Nine fire engines attended a house in Sherwood Way after a witness described an “almighty crash” and a hole straight through the roof with flames coming out.
- One night in June 2026. Overnight thunderstorms on 27 June set off a string of lightning fires across Kent and Sussex, with homes hit in Faversham, Ulcombe, Crawley, Bexhill and Eastbourne. In south London the same night, lightning destroyed the roof of a shop with homes above it on Mitcham Lane in Streatham.
Most of those are private homes, which aren’t covered by the Fire Safety Order. We’ve included them to show how often lightning fires happen in our area. But look at the pattern. Fire in the roof. Fire spreading to the building next door through a shared roof space. Several buildings hit by one strike. Every one of those patterns applies just as much to a terrace of shops, an office block, an HMO or a school.
What a lightning protection system does
A lightning protection system doesn’t stop lightning hitting your building. What it does is give the current a safe, planned route to the ground, so it doesn’t go looking for its own route through your roof timbers and wiring.
A typical system has three main parts:
- Air terminations. These are the conductors at the top of the building, such as rods, tapes along the ridge or a mesh across a flat roof. They’re designed to be the point the lightning hits.
- Down conductors. These are the metal tapes or cables that run down the outside of the building, carrying the current from the roof to the ground.
- Earth termination. This is the system of rods or plates buried in the ground that spreads the current safely into the earth.
On top of that, the system is bonded to other metalwork in the building, such as pipes, steel frames and service entries, so that the current doesn’t jump across gaps and cause sparks. That bonding is one of the first things to go wrong when buildings are altered. A new extension, solar panels, a new roof, an aerial or a satellite dish can all change how the system works, and the person fitting them might have no idea the system is there.
Surge protection: the part people forget
Here’s the thing many building owners don’t realise. A lightning protection system on the roof deals with direct strikes. It does very little about surges coming in along the cables, which is what happened at Tilehurst. For that, you need surge protection.
Surge protective devices, or SPDs, are fitted in the electrical installation, usually at the main distribution board, and sometimes on data, phone and aerial lines too. When a surge arrives, the SPD diverts it safely to earth before it reaches the equipment, or the wiring, downstream.
From a fire safety point of view, surge protection matters for two reasons. First, a surge can overheat wiring and start a fire, sometimes a long way from where it came in. Second, a surge can damage the systems your fire strategy depends on. That includes the fire alarm panel, emergency lighting, door holders that release fire doors, access control on escape doors, smoke ventilation and sprinkler pumps. As the Havant school showed, an alarm can be affected even when there’s no fire at all.
The wiring regulations, BS 7671, now require surge protection in many situations, including where an overvoltage could cause serious injury or loss of life, interrupt public services or damage cultural heritage. Older installations often don’t have it. Your fire risk assessor won’t usually test it, but they should ask whether it’s there, and your Electrical Installation Condition Report (EICR) should say. If the two reports don’t talk to each other, gaps appear. Our article on the Clandon Park fire shows what can happen when an electrical risk falls between two reports.
Which buildings are higher risk?
Every building can be hit, but some are far more exposed, and some would suffer far worse consequences. Your assessment should take a closer look at lightning if your building is:
- Tall or has tall features. Towers, spires, chimneys, masts, flagpoles and tall blocks of flats.
- Isolated or on high ground. A building on a hilltop or in open countryside is often the tallest thing around, like the church at Abinger.
- Built with combustible materials. Timber-framed buildings, thatched roofs, and buildings with large timber roof voids.
- Historic or listed. Old buildings often have large, open roof voids with no compartmentation, and what’s inside them can’t be replaced.
- Home to people who can’t easily escape. Care homes, hospitals, sheltered and supported housing, and any building where people sleep.
- Busy. Schools, places of worship, offices, shopping centres and venues.
- Storing flammable materials. Fuel, gas, chemicals, solvents, hay and straw, waste, or anything that creates a flammable atmosphere.
- Providing essential services. Buildings whose loss would cut off something the public depends on.
Thatch deserves a special mention. In May 2024, lightning is believed to have started a fire that gutted a pair of thatched cottages at Stoborough, near Wareham in Dorset, and the fire spread quickly from one roof to the next. Local reporting noted the cottages didn’t have fire boards, the fire-resisting boards fitted under thatch to slow a fire’s spread into the building. If you own or manage a thatched building, lightning protection and fire boards both deserve a serious look.
Testing and inspection
A lightning protection system sits outside, in all weathers, for decades. Tapes come loose. Clamps corrode. Roofers move conductors and don’t put them back. Thieves steal copper. And the earth resistance at the bottom of the system changes as the ground dries out or gets disturbed.
That’s why systems need regular inspection and testing. BS EN 62305 sets intervals based on the level of protection the building needs. For churches, Ecclesiastical Insurance recommends an inspection preferably every 12 months and no more than four years apart, with two years for the highest protection levels. Many contractors test every 11 months, so that the test moves through the seasons and the system gets checked in both wet and dry ground conditions over time.
A proper inspection should include:
- a visual check of all the conductors, fixings, joints and test clamps
- a check that the system still matches the building, including any extensions, new plant or roof work
- earth resistance testing at each test point
- continuity testing, to make sure the conductors are properly connected all the way through
- a check of the bonding to other metalwork and services
- a written report, with any defects and what needs doing about them
Keep that report with your fire risk assessment. When your assessor visits, they’ll want to see it, and it’s much easier for them to give an accurate picture if the evidence is there.
What to do next: a practical checklist
If you’re the responsible person for a building, here’s how to get lightning properly into your fire risk assessment.
- Find out what you’ve got. Does your building have a lightning protection system? Look for metal tapes running down the outside walls and test clamps near ground level. If you’re not sure, ask your maintenance contractor or check your building records.
- Find the paperwork. Look for the original design, any BS EN 62305-2 risk assessment, and the most recent test report. If there’s no test report from the last year or so, book one.
- Check your surge protection. Your most recent EICR should say whether surge protective devices are fitted. If it doesn’t, ask your electrician.
- Think about what’s changed. Have you added solar panels, an extension, rooftop plant, a phone mast, aerials or new cladding since the system was designed? Each one could affect how it works.
- Talk to your fire risk assessor. Make sure lightning is covered properly in your assessment, not just ticked. Ask them to link it to your fire alarm, emergency lighting and escape plan.
- Check what’s behind the walls and in the roof. If lightning does start a fire, compartmentation, cavity barriers and fire stopping are what keep it in one place. A compartmentation survey will tell you whether yours would do the job.
- Plan for the aftermath. Lightning fires often happen when buildings are empty, like Lytchett Minster at Christmas. Make sure your emergency plan covers who gets called, how the building is secured, and what gets saved first.
- Talk to your insurer. Many insurers have specific requirements for lightning protection, especially for churches, heritage buildings and industrial sites. Check that you’re meeting them.
How ESI can help
We carry out fire risk assessments across Surrey, Berkshire and Hampshire, from our base in Camberley and our office in Reading. When we assess a building, we look at lightning as a real source of ignition, not a box to tick. We’ll ask about your system, your surge protection and your test records, and we’ll tell you plainly whether they’re good enough for the building you’ve got.
If you’d like your fire risk assessment reviewed, or you’re not sure whether lightning has been covered properly, get in touch and we’ll talk it through.
Frequently asked questions
Is lightning protection a legal requirement in the UK?
Not for every building. There’s no law that says all buildings must have a lightning protection system, and it isn’t a Building Regulations requirement. But under the Fire Safety Order, you must assess your fire risks and act on what you find. If lightning is a significant risk for your building, you’re expected to deal with it. Insurers may also require a system as a condition of cover.
Should my fire risk assessment mention lightning?
Yes. Lightning is a source of ignition, and a suitable and sufficient fire risk assessment should consider it. PAS 79, which most UK assessors work to, includes lightning in the list of things to consider. For many small, low buildings, the answer will be that the risk is low. For taller, isolated, historic or high-occupancy buildings, it should get a closer look.
Does a fire risk assessor test the lightning protection system?
No. Testing is specialist work carried out by a lightning protection engineer. Your fire risk assessor should ask whether a system is fitted, look at the most recent test report, and note any obvious visible problems. If there’s no recent test report, they’ll usually recommend getting one.
How often should lightning protection be tested?
BS EN 62305 sets intervals based on the protection level your building needs. Ecclesiastical Insurance recommends that church systems are inspected preferably every 12 months and no more than four years apart, with two years for the highest protection levels. Many contractors test every 11 months so the test falls in different seasons over the years. Systems should also be checked after any known strike and after any building work that might affect them.
What is BS EN 62305?
It’s the British and European standard for protecting buildings against lightning. It has four parts. Part 2 covers risk management, which is the method for working out whether a building needs protection and what level. Part 3 covers the physical protection of buildings, and Part 4 covers electrical and electronic systems inside them.
What’s the difference between lightning protection and surge protection?
A lightning protection system deals with direct strikes on the building, giving the current a safe route to the ground. Surge protection deals with surges that come in along cables, such as the power supply, phone lines and aerials. You can have one without the other, but most at-risk buildings need both. The Tilehurst fire, where a surge came down a TV aerial cable, is an example of why.
Can lightning damage my fire alarm?
Yes. A strike or a surge can damage fire alarm panels, detectors and the wiring between them. When lightning hit a primary school in Havant in January 2025, the fire service said the strike caused the alarm to malfunction. Surge protection on the electrical supply and the alarm system reduces that risk. After any strike, have your alarm checked by a competent engineer.
Do blocks of flats need lightning protection?
It depends on the building. Height, location, construction and the number of residents all affect the risk. The Fire Industry Association published a screening tool in June 2026 to help assess existing lightning protection arrangements in residential buildings. It gives a simple answer on whether the arrangements need further looking into. Your fire risk assessor can help you use it.
Does lightning only strike in summer?
No. Most UK thunderstorms happen in summer, but lightning can strike at any time of year. Lytchett Minster School was struck on 27 December, and the Havant school was struck on 27 January.
What should I do if my building is struck by lightning?
If there’s any sign of fire, smoke or burning smells, get everyone out and call 999. Fires from lightning can smoulder in roof spaces and walls for hours before they show, as the Peckham fire showed. Even if there’s no obvious damage, have the building checked. That includes the lightning protection system, the electrical installation, the fire alarm and emergency lighting. Tell your insurer, and update your fire risk assessment if anything has changed.